The interconnected thermal power system consists of several areas. Various parameters should be provided to reach power systems’ firm operation. The current work proposed an optimization algorithm, namely Ant colony optimization (ACO) to optimize the Proportional-Integral-Derivative (PID) controller for the load frequency control of two-area interconnected non-reheat thermal power system with Governor dead band nonlinearity. The ACO in used to determine optimal controller’s parameters, where an objective function, namely Integral Time Absolute Error is conducted. A comparative study for the ACO performance to the Craziness based Particle swarm optimization (CPSO) is studied to examine the proposed approach performance in the interconnecting thermal power system. The result established the ACO optimized PID controller response superiority of the compared to the CPSO optimized controller.